MYCHARGEMAN Forum

Members Login
Username 
 
Password 
    Remember Me  

Topic: Current Transformer Test

Post Info
Koperal
Status: Offline
Posts: 50
Date:
Current Transformer Test
Permalink  
 

CT details:function Disciminating zone

Ratio= 3000/1A

Class = X 

VA= 30VA

Rated Volt= 145kv

 

1) insulation test

2) Polarity test

3) DC resistance test

4) magnetisation test

5) Ratio at rated burden test

6) primary injection test



__________________
Staff Sarjan
Status: Offline
Posts: 170
Date:
Permalink  
 
good info..mcm mana kaedah pengujian nya pula?? share sket

__________________
ZD
Koperal
Status: Offline
Posts: 50
Date:
Permalink  
 

1) pengujian melakukan insullation test

      Primary to Earth

      Secondry to Earth

      Primary to Secondry

2) Polarity test

      untuk menentukan keduudukan P1-P2 Dan S1-S2 pada CT adlah betul..

3) DC resistance test

      Mengukur Nilai resistance pada winding CT dengan injection DC voltage measure       resistance pada CT..

4) Magnetisation test..

    Membuat graf voltan dan arus knee point(tepu) pada CT..injection voltage pada S1     dan S2 dengan mengambil nilai arus kenaikan sebanyak 50% dan voltage 10%           sehingga dapat nilai knee point CT..

5) Ratio at Rated Burden

    Menguji nilai burden VA pada CT dengan menyikut name plate CT..inject current pada P1-P2 kemudian pada S1-S2 disambung pada resistence dengan nilai resistance gunakan fomula VA=I2/R..inject current menyikut nilai ratio CT measure voltage dan current kemudian calculate kedua2nye..

6) Primary injection Test..

   Menguji CT circuit sehingga ke relay protection atau metering..inject current pada P1-P2 Kemudian measure pada secondry di relay protection atau metering..Lakukan setiap phase..

 

kerja2 Testing dilakukan di Site pada CT High Voltage..

 



__________________
Laksamana Muda
Status: Offline
Posts: 1145
Date:
Permalink  
 
Reading untuk 6 ujian tu pulak?

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

Koperal
Status: Offline
Posts: 50
Date:
Permalink  
 

reading untuk test kene ikut expected manufacturing dan standart SAT procedure..(site accepted test)



__________________
Laksamana Muda
Status: Offline
Posts: 1145
Date:
Permalink  
 
i see..

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

Staff Sarjan
Status: Offline
Posts: 170
Date:
Permalink  
 
good..

__________________
ZD
Page 1 of 1  sorted by