(SEAWARD PR 11)

 

PHASING STICK

 

1.      GENERAL

 

Phasing stick is used in high voltage installation for phase testing between two terminals before connection is made. It is also used as a voltage indicator for 11kV installation.

 

2.      COMPONENT OF PHASING STICKS

 

a.       Live Conductor Tester

 

Conductor tester is basically a paper (resin) indulted rod and the handle of it is rubber covered. The whole rod is 98cm in length. It has a contact piece at the end of the rubber covered handle to which the lead are connected. It also has a voltmeter connected to it. The voltmeter has a 0 – 15kV scale. Each division on the voltmeter represents 1 kV.

 

b.      The Phasing Rod

 

This is similar to the live conductor tester. The only difference is that the voltmeter is omitted.

 

c.       The Proving Unit

 

The proving unit is used to test that the phasing rod, the live conductor and the voltmeter are in good condition. The proving unit has a ‘HT’ casket, a variable resistance knob, a test switch S, a test lead plug P and earth terminal E and also an HT indication bulb.

 

The proving operates on dry batteries to produce a high voltage of approximate 5kV. Each battery is 4.5 V and a total of 3 batteries connected in series are used. The batteries are externally kept and connected to the proving unit by means of two terminals from the proving unit itself. The terminals are marked red and blue which are connected to the positive and negative of the batteries respectively.

 

d.      Extension Rod

 

An extension rod of 99.5 cm is available and can be fitted to the phasing rod or live conductor tester.

 

There is also an adaptor, which is bent at an angle so as to be used in difficult situations. This adaptor can be fitted to either phasing stick or even to the extension rod itself.

 

 

e.       Test Leads

 

The test leads are given to aid in phasing out as well as for testing the phasing sticks.

 

Three types of leads are given

i.        which is fitted at both ends with a jack

ii.      which is fitted at one end with a clip and the other end has a socket

iii.    which has one end fitted with a jack and the other end with a clip

 

f.       Casing

 

All the phasing equipment are placed in a wooden case which measures 140cm x 35cm x 60.5cm.



-- Edited by MAC Admin on Saturday 7th of May 2011 01:36:02 AM



-- Edited by MAC Admin on Saturday 7th of May 2011 01:37:40 AM

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

Rekrut
Status: Offline
Posts: 2
Date:
Permalink  
 
maklumat yg sngat berguna....trima kasih...

__________________
Laksamana Muda
Status: Offline
Posts: 1145
Date:
Permalink  
 
Sama-sama share.. cuma gambar tak dapat keluar.. cuti kot..

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

Staff Sarjan
Status: Offline
Posts: 170
Date:
Permalink  
 
good..

__________________
ZD
Rekrut
Status: Offline
Posts: 2
Date:
Permalink  
 
Ada siapa pernah pakai seaward PR15D boleh advice sikit macamana nak guna?

__________________
Laksamana Muda
Status: Offline
Posts: 1145
Date:
Permalink  
 
meor_9 boleh try check di ruangan download:

http://mychargeman.activeboard.com/t53159841/free-download-pdf-seaward-manuals-compilation-1/?page=last#lastPostAnchor

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

 
Page 1 of 1  sorted by
Quick Reply

Please log in to post quick replies.



Create your own FREE Forum
Report Abuse
Powered by ActiveBoard