This test is to make sure the transformer ratio, say 11,000/433V is true. Apply lower, safe and easy to calculate value of voltage, say 110V to the HV side of the transformer and measure voltage induced at the LV terminal. The voltage at the secondary LV side should be in the same ratio as the above ratio. It should be 4.33 volt between phases or 2.4 volt between phase and neutral.
6.4Oil Breakdown Voltage Test
It has been explained in the previous topic.
6.5Pressure Test
Apply 30 kV DC voltage between all the three phases on the HV side only and check the leakage current whether it is in the acceptable value.
__________________
Henry Ford Coming together is a beginning. Keeping together is progress. Working together is success.
dy1 n dy11..merujuk pada jenis sambungan transfomer HV DELTA(d)..LV STAR(y)..angka yg teakhir adalah nilai kedudukan winding menghadap HV dan LV..untuk menentukan dy1 atau dy11 dipanggil vector group TX..ujian vector group perlu dilakukan baru kt dapat mengetahui kedudukan winding HV dan LV..dengan melakAR betuk vector winding TX..
CARA PEGUJIAN..
shot winding Red phase HV dengan winding Red phase LV..apply voltage pada HV side 3 PHASE 415V dengan pada tap changer normal tap..kemudian measure setiap phase iaitu AB BCCA AN BN CN Aa Ab Ac Nc
BaBbBc NbCa CbCc NcAaAb' abac bc an bn cnAc'Ba'Bb'Bc'
kemudian lukis vector diagram dengan memasukan nilai voltage yg di measure tadi..menyikut scale yg dibuat contoh 30v=1cm..vector tersebut akan menenujukkan nilai dy1 atau dy11..
apa sebab diwujudkan dy1 n dy11? adakah ia mempengaruhi phase sequence & phase angle?? jika dalam protection kita tahu bahawa perbezaan antara negetive sequence (0) dan juga positive sequence (1)..adakah ia berkaitan??
tidak mempengaruhi phase angle..dy11 n dy1 dapt dilihat dengan melukis satu lakaran vector bagi menentukan kedudukan 1 atau 11 same seperti dalam name plate TX..