SAIZ KAPASITOR BANK
Untuk menentukan saiz kapasitor yang diperlukan, formula berikut boleh digunakan:
Pr = Pw (tan θ1 – tan θ2)
= Pw x k
Dimana, Pr Kadar kapasitor dalam KVAr
Pw Beban pepasangan dalam KW
Kos θ1 Faktur kuasa asal
Kos θ2 Faktur kuasa diperbaiki
k Nilai k boleh diperolehi dari Jadual faktur
k atau nomogram
Henry Ford Coming together is a beginning. Keeping together is progress. Working together is success.
MFC Commissioner [OFFICIAL] CODE: 1601
IEEE Members CODE: 92905849
@Bahaya Elektrik
@CMC Student Branch
@Standard Gaji Chargeman
dh betul la 2....
hehehe
e_xbetoi wrote:betul x formula nk cri C/K setting C/K = kvar1.732 x V x ct ratioor ada formula lain......
betul x formula nk cri C/K setting
C/K = kvar
1.732 x V x ct ratio
or ada formula lain......