Topic: kabel servis n bekalan

Post Info
Lans Koperal
Status: Offline
Posts: 30
Date:
kabel servis n bekalan
Permalink  
 

npe klo kabel sesalur ABC 185 & 95,saiz neutral lbh kecik dan npe kabel servis ABC 16 & 25 lg besar?bley bg komen?aq nk kompare ngn jwpn aq  



__________________

Amp Like A Blood

Volt Is The Body

always related

Laksamana Muda
Status: Offline
Posts: 1145
Date:
Permalink  
 
Pernah dengar soalan ni..

__________________

Henry Ford
Coming together is a beginning. Keeping together is progress. Working together is success.

MFC Commissioner [OFFICIAL] CODE: 1601

IEEE Members CODE: 92905849

@Bahaya Elektrik 

@CMC Student Branch 

@Standard Gaji Chargeman 

amy
Lans Koperal
Status: Offline
Posts: 20
Date:
Permalink  
 
same jugak mcm sungai...kenapa orang mandi kat sungai yg kecik je...orang x mandi kat sungai pahang....perlu kn detail lg ke???hehe

__________________
Lans Koperal
Status: Offline
Posts: 30
Date:
Permalink  
 
mybe amy ptt d sepak...hehehe

__________________

Amp Like A Blood

Volt Is The Body

always related

amy
Lans Koperal
Status: Offline
Posts: 20
Date:
Permalink  
 
bro...kabel ABC bersaiz 185 & 95 biase gune untuk voltan tinggi bro...
beban voltan tinggi x gune neutral, kabel tue hanye untuk pembumian...
kabel kecik gune untuk voltan rendah...voltan rendah kebanyakan beban gune neutral...
arus pd neutral lebih tinggi dari arus pada kabel fasa sbb arus balikan dr R,Y,B semua ke neutral..
tue je sebab nye

__________________
Lans Koperal
Status: Offline
Posts: 30
Date:
Permalink  
 
tq amy,btol 2...pendapat aq pown lbh kurang nie.... 2 la mslh yg kte adapi pd voltan rendah nie..klo load ok xpe la..klo load x balance neutral la penyelamat die an...

__________________

Amp Like A Blood

Volt Is The Body

always related

Lans Koperal
Status: Offline
Posts: 30
Date:
Permalink  
 
hak3..sowie ea kpd sume....nk wat correction ckit la...nie kompem gle jwpn yg agk tepat..npe neutral ag bsr dr fsa bg sesalur bekalan(servis) & neutral pd kabel 185 & 95(main line) ag kecik?
bg main line,neutral die kck sbb die xd load ag...it just like tranmission line...so xpe...
Tp bg servis line pulak,ianya talian yg smpi ke rumh2 kte...jd ad load...jike x ballance,nuetral akan return dlm satu2 circuit..dan kabel neutral hnya 1 je bg kesuluruhan talian..klo fasa kte ad 3.x hairan la neutral ag bsr..plus bhn buatan neutral adlh drpd drawn high aluminium(aluminium tarikan keras)..mmg kompem ag keras drpd fasa(aluminium sje..)klo slah tlg btolkan ea..